Spirit Thermostatic Valve

This describes the Z-Wave device Spirit, manufactured by Eurotronics with the thing type UID of eurotronic_spirit_00_000.

The device is in the category of Radiator Control, defining Controls on radiators used to heat up rooms.

Spirit product image

The Spirit supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is unable to participate in the routing of data from other devices.

Overview

Spirit Z-Wave Plus is a Z-Wave radio standard compatible energy-saving radiator thermostat.

FLiRS (Frequently Listening Receiver Slave): Spirit Z-Wave uses FLiRS to provide short latency and short responding times.

Inclusion Information

Start Inclusion mode of your primary Z-Wave Controller. Press the Boost-Button. Spirit Z-Wave Plus will show the assigned NodeID.

Exclusion Information

Start Exclusion mode of your primary Z-Wave Controller. Now press and hold the boost button of the Spirit Z-Wave Plus for at least 5 seconds.

Channels

The following table summarises the channels available for the Spirit -:

Channel Channel Id Category Item Type
Dimmer switch_dimmer DimmableLight Dimmer
Current temperature sensor_temperature Temperature Number:Temperature
External temperature sensor_report Number
Thermostat mode thermostat_mode Temperature Number
Setpoint (heat) thermostat_setpoint Temperature Number:Temperature
Setpoint (energy heat) thermostat_setpoint Temperature Number:Temperature
Alarm (system) alarm_system Switch
Alarm (power) alarm_power Door Switch
Battery Level battery-level Battery Number

Dimmer

The brightness channel allows to control the brightness of a light. It is also possible to switch the light on and off.

The switch_dimmer channel supports the Dimmer item and is in the DimmableLight category.

Current temperature

Indicates the current temperature.

The sensor_temperature channel supports the Number:Temperature item and is in the Temperature category.

External temperature

Send report to device.

The sensor_report channel supports the Number item.

Thermostat mode

Sets the thermostat.

The thermostat_mode channel supports the Number item and is in the Temperature category. The following state translation is provided for this channel to the Number item type -:

Value Label
0 Off
1 Heat
2 Cool
3 Auto
4 Aux Heat
5 Resume
6 Fan Only
7 Furnace
8 Dry Air
9 Moist Air
10 Auto Changeover
11 Heat Economy
12 Cool Economy
13 Away

Setpoint (heat)

Precision 0,1 and 2 Scale Celsius and Fahrenheit Temp. Range 8°C-28°C

Sets the thermostat setpoint.

The thermostat_setpoint channel supports the Number:Temperature item and is in the Temperature category.

Setpoint (energy heat)

Precision 0,1 and 2 Scale Celsius and Fahrenheit Temp. Range 8°C-28°C

Sets the thermostat setpoint.

The thermostat_setpoint channel supports the Number:Temperature item and is in the Temperature category.

Alarm (system)

Indicates if a system alarm is triggered.

The alarm_system channel supports the Switch item. This is a read only channel so will only be updated following state changes from the device.

The following state translation is provided for this channel to the Switch item type -:

Value Label
OFF OK
ON Alarm

Alarm (power)

Indicates if a power alarm is triggered.

The alarm_power channel supports the Switch item and is in the Door category. This is a read only channel so will only be updated following state changes from the device.

The following state translation is provided for this channel to the Switch item type -:

Value Label
OFF OK
ON Alarm

Battery Level

Represents the battery level as a percentage (0-100%). Bindings for things supporting battery level in a different format (e.g. 4 levels) should convert to a percentage to provide a consistent battery level reading.

The battery-level channel supports the Number item and is in the Battery category.

Device Configuration

The following table provides a summary of the 8 configuration parameters available in the Spirit. Detailed information on each parameter can be found in the sections below.

Param Name Description
1 LCD Invert LCD Invert
2 LCD Timeout LCD Timeout
3 Backlight Backlight
4 Battery report Battery report
5 Measured Temperature report Measured Temperature report
6 Valve opening percentage report Valve opening percentage report
7 Window open detection Window open detection
8 Temperature Offset Measured Temperature offset

Parameter 1: LCD Invert

LCD Invert

The following option values may be configured -:

Value Description
0 LCD-content normal
1 LCD-content inverted (UK Edition)

The manufacturer defined default value is 0 (LCD-content normal ).

This parameter has the configuration ID config_1_1 and is of type INTEGER.

Parameter 2: LCD Timeout

LCD Timeout 0: No Timeout LCD always on

5-30: LCD will turn off after 5 to 30 seconds The following option values may be configured, in addition to values in the range 5 to 30 -:

Value Description
0 No Timeout LCD always on

The manufacturer defined default value is 0 (No Timeout LCD always on).

This parameter has the configuration ID config_2_1 and is of type INTEGER.

Parameter 3: Backlight

Backlight

The following option values may be configured -:

Value Description
0 Backlight disabled
1 Backlight enabled

The manufacturer defined default value is 1 (Backlight enabled).

This parameter has the configuration ID config_3_1 and is of type INTEGER.

Parameter 4: Battery report

Battery report

The following option values may be configured -:

Value Description
0 system notification
1 Send battery status unsolicited once a day.

The manufacturer defined default value is 1 (Send battery status unsolicited once a day. ).

This parameter has the configuration ID config_4_1 and is of type INTEGER.

Parameter 5: Measured Temperature report

Measured Temperature report 0: Unsolicited Temperature reporting disabled

1-50: report if temperature changed by delta = 0,1°C ... 5,0 °C

default 5: report on delta T = 0,5°C Values in the range 0 to 50 may be set.

The manufacturer defined default value is 5.

This parameter has the configuration ID config_5_1 and is of type INTEGER.

Parameter 6: Valve opening percentage report

Valve opening percentage report 0: Unsolicited valve opening percentage reporting disabled.

1-100: report if valve opening changed by delta = 1% ... 100% Values in the range 0 to 100 may be set.

The manufacturer defined default value is 0.

This parameter has the configuration ID config_6_1 and is of type INTEGER.

Parameter 7: Window open detection

Window open detection

The following option values may be configured -:

Value Description
0 Disabled
1 Sensitivity low
2 Sensitivity medium
3 Sensitivity high

The manufacturer defined default value is 2 (Sensitivity medium).

This parameter has the configuration ID config_7_1 and is of type INTEGER.

Parameter 8: Temperature Offset

Measured Temperature offset -50 - +50: Offsets the measured temp by-5,0°C – (+)5,0°C

128: External temp sensor will be used for regul. The following option values may be configured, in addition to values in the range -50 to 50 -:

Value Description
128 Ext temp sensor be used for regul

The manufacturer defined default value is 0.

This parameter has the configuration ID config_8_1 and is of type INTEGER.

Association Groups

Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.

The Spirit supports 1 association group.

Group 1: Lifeline

The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation. Spirit Z-Wave Plus can only be associated with the Z-Wave controller. Commands:

BATTERY_REPORT, DEVICE_RESET_LOCALLY_NOTIFICATION, THERMOSTAT_MODE_REPORT, THERMOSTAT_SETPOINT_REPORT, NOTIFICATION_REPORT, PROTECTION_REPORT, SENSOR_MULTILEVEL_REPORT, SWITCH_MULTILEVEL_REPORT

Association group 1 supports 1 node.

Technical Information

Endpoints

Endpoint 0

Command Class Comment
COMMAND_CLASS_NO_OPERATION_V1
COMMAND_CLASS_BASIC_V1
COMMAND_CLASS_SWITCH_MULTILEVEL_V1
COMMAND_CLASS_SENSOR_MULTILEVEL_V5
COMMAND_CLASS_THERMOSTAT_MODE_V3
COMMAND_CLASS_THERMOSTAT_SETPOINT_V3
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_CONFIGURATION_V1
COMMAND_CLASS_ALARM_V8
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1
COMMAND_CLASS_POWERLEVEL_V1
COMMAND_CLASS_PROTECTION_V1
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V3
COMMAND_CLASS_BATTERY_V1
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_SECURITY_V1