layout | title |
---|---|
documentation |
IS140-2 - ZWave |
{% include base.html %}
This describes the Z-Wave device IS140-2, manufactured by Steinel with the thing type UID of steinel_is1402_00_000
.
The device is in the category of Motion Detector, defining Motion sensors/detectors.
The IS140-2 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.
PIR sensor with relay, mains powered 230-240 V, 50 Hz
- Output Incandescent lamps, max. 1000 W at 230 V AC
- Fluorescent lamp, max. 500 VA at cos = 0.5,
- inductive load at 230 V AC
- LED lamps, max. 6 × 58 W, C ≤ 132 μF at 230 V AC *1)
- Z-Wave wireless range approx. 100 m (unobstructed line of vision)
To start the motion detector's inclusion, turn the device's control dial to "Set" and back to "0" within 5 seconds.
To start the motion detector's exclusion mode, turn the device's control dial to "Set" and back to "0" within 5 seconds.
Following exclusion, all configuration parameters (time, sensitivity etc.) remain intact until next inclusion and the light now works in standalone mode – as a result, Z-Wave can also be used for the light’s standalone setting. Z-Wave control dial (E) Control dial for inclusion and exclusion as well as for returning the device to the factory setting.
The following table summarises the channels available for the IS140-2 -:
Channel | Channel Id | Category | Item Type |
---|---|---|---|
Switch | switch_binary | Switch | Switch |
Scene Number | scene_number | Number | |
Binary Sensor | sensor_binary | Door | Switch |
Sensor (luminance) | sensor_luminance | Number | |
Alarm (burglar) | alarm_burglar | Door | Switch |
Alarm (system) | alarm_system | Switch | |
Motion Alarm | alarm_motion1 | Door | Switch |
Sensor (luminance) | sensor_luminance2 | Number | |
Relay Switch | switch_binary3 | Switch | Switch |
Switch the power on and off.
The switch_binary
channel supports the Switch
item and is in the Switch
category.
Triggers when a scene button is pressed.
The scene_number
channel supports the Number
item.
Indicates if a sensor has triggered.
The sensor_binary
channel supports the Switch
item and is in the Door
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
ON | Triggered |
OFF | Untriggered |
Indicates the current light reading.
The sensor_luminance
channel supports the Number
item. This is a read only channel so will only be updated following state changes from the device.
Indicates if the burglar alarm is triggered.
The alarm_burglar
channel supports the Switch
item and is in the Door
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Indicates if a system alarm is triggered.
The alarm_system
channel supports the Switch
item. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Indicates if a motion alarm is triggered.
The alarm_motion1
channel supports the Switch
item and is in the Door
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Indicates the current light reading.
The sensor_luminance2
channel supports the Number
item. This is a read only channel so will only be updated following state changes from the device.
Switch the power on and off.
The switch_binary3
channel supports the Switch
item and is in the Switch
category.
The following table provides a summary of the 15 configuration parameters available in the IS140-2. Detailed information on each parameter can be found in the sections below.
Param | Name | Description |
---|---|---|
1 | Time | Duration of light after motion detection |
2 | Light | Light threshold |
5 | Sensitivity | Motion Radar Sensitivity |
8 | Global_Light | External ambient light value |
9 | SLAVE_MODE | Disable local control |
9 | Bit 0: Slave Mode | 0=Disable, 1=Enable |
9 | Bit 1: Central Unit checking | 0=Disable, 1=Enable |
9 | Bit 2: Stupid Mode | 0=Disable, 1=Enable |
10 | (OFF_BEHAVIOUR) | Off behaviour (timeout) |
11 | ON_BEHAVIOUR | On behaviour (timeout) |
12 | ON_TIME_OVER | On behaviour time over (timeout) |
13 | ON_OFF_ BEHAVIOUR | Sequence On-Off behaviour (timeout) |
14 | OFF_ON_ BEHAVIOUR | Sequence Off-On behaviour (timeout) |
15 | SEQUENCE_ TIME | Sequence timing |
16 | MOTION_ DISABLE | Motion Off behaviour (timeout) |
Switch All Mode | Set the mode for the switch when receiving SWITCH ALL commands |
Duration of light after motion detection
Values in the range 5 to 900 may be set.
The manufacturer defined default value is 180
.
This parameter has the configuration ID config_1_2
and is of type INTEGER
.
Light threshold
0 – run Learn ambient light sequence.
2000 – is used as daylight (always night mode).
Value can be controlled via potentiometer (if present on device) – potentiometer value is then used as the default value and any potentiometer movement rewrites the current setting.
Values in the range 0 to 2000 may be set.
The manufacturer defined default value is 2000
.
This parameter has the configuration ID config_2_2
and is of type INTEGER
.
Motion Radar Sensitivity Value can be controlled via potentiometer (if present on device) – potentiometer value is then used as the default value and any potentiometer movement rewrites the current setting. Values in the range 2 to 100 may be set.
The manufacturer defined default value is 100
.
This parameter has the configuration ID config_5_1
and is of type INTEGER
.
External ambient light value
When GLOBAL_LIGHT mode is ON – device overrides its own light sensor values and uses Light Report values from any Z-Wave light sensor instead – this has to be configured appropriately to send light automatically.
If the last remote light level value is older than 30 minutes, the internal light value is used again until the next external value is received.
Values in the range 0 to 1 may be set.
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_8_1
and is of type INTEGER
.
Disable local control This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 4 may be set.
The manufacturer defined default value is 2
.
This parameter has the configuration ID config_9_1
and is of type INTEGER
.
0=Disable, 1=Enable Slave mode (bit 0 =1):
- only if included in Z-Wave network
- useful for controlling via third-party sensor
- lamp/relay is directly controlled via Z-Wave, internal sensors are not used for controlling it The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 1
(Enable).
This parameter has the configuration ID config_9_1_00000001
and is of type INTEGER
.
0=Disable, 1=Enable Central unit checking (bit 1 =1): (useful especially for controlling via gateway)
When slave bit is 0:
- device signalises fail of lifeline connection (if this bit is zero, fail of lifeline connection is not signalised)
When slave bit is 1:
- device checks presence of Z-Wave device in lifeline group (gateway).
If it is not present for 2 minutes (testing repeatedly every 30 seconds) device switches to normal mode in the same way as after the end of local disabled mode (ON_BEHAVIOUR)
- the device checks every 1 minute for recovery of lifeline connection
- if no lifeline specifed - it works in normal mode The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 1
(Enable).
This parameter has the configuration ID config_9_1_00000002
and is of type INTEGER
.
0=Disable, 1=Enable "Stupid" mode (bit 2 = 1):
- has higher priority then slave mode
- lamp/relay is permanently on (for simple power wall switch controlling) The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 0
(Disable).
This parameter has the configuration ID config_9_1_00000004
and is of type INTEGER
.
Off behaviour (timeout) Behaviour after BASIC OFF (and similar commands). If a transition (even with zero change) with a non-default duration is to be processed, the transition cannot be interrupted by any motion event in any case.
0 = Lamp/Relay is switched off and remains so until any new motion event (local or remote) is received.
1 - 209 = Lamp/Relay is switched off and remains so until after a specified timeout once a new motion event (local or remote) is received.
Timeout:
- 1..100 – 1 second (1) to 100 seconds (100) in 1-second resolution
- 101..200 – 1 minute (101) to 100 minutes (200) 1-minute resolution
- 201..209 – 1 hour (201) to 9 hours (209) in 1-hour resolution
- 210 - 254 = Reserved
- 255 = Lamp/relay is switched off for TIME (cfg 1). It does not wait for a motion event and works normally via current motion evaluation. Values in the range 0 to 255 may be set.
The manufacturer defined default value is 10
.
This parameter has the configuration ID config_10_2
and is of type INTEGER
.
On behaviour (timeout) Behaviour after BASIC ON (and similar commands). If a transition (even with zero change) with a non-default duration is to be processed, the transition cannot be interrupted by any motion event in any case.
0 = Lamp/relay is switched on and remains so until any new motion event (local or remote) is received. It then works normally via current
motion evaluation.
Notice – during the day, this mode cannot be ended remotely due
to motion events not being transmitted – only via local motion sen-
sor if enabled.
1 - 209 = Lamp/relay is switched on and remains so until after a specified timeout once a new motion event (local or remote) is received. It then
works normally via current motion evaluation.
Timeout:
- 1..100 – 1 second (1) to 100 seconds (100) in 1-second resolution
- 101..200 – 1 minute (101) to 100 minutes (200) in 1-minute resolution
- 201..209 – 1 hour (201) to 9 hours (209) in 1-hour resolution
Notice – during the day, this mode cannot be ended remotely due to motion events not being transmitted – only via local motion sensor if
enabled. - 210 - 254 = Reserved
- 255 = Lamp/relay is switched on for TIME (cfg 1). It does not wait for a motion event and works normally via current motion evaluation. Values in the range 0 to 255 may be set.
The manufacturer defined default value is 255
.
This parameter has the configuration ID config_11_2
and is of type INTEGER
.
On behaviour time over (timeout) Time limit to stop waiting for motion after timeout of ON_BEHAVIOUR or OFF_ON_BEHAVIOUR (0-209) to prevent staying ON forever when there is no motion.
- 0 = No additional waiting for motion.
- 1 - 209 = 1..100 – 1 second (1) to 100 seconds (100) in 1-second resolution
- 101..200 – 1 minute (101) to 100 minutes (200) in 1-minute resolution
- 201..209 – 1 hour (201) to 9 hours (209) in 1-hour resolution
- 210 - 254 = Reserved
- 255 = Never stop waiting for motion. Values in the range 0 to 255 may be set.
The manufacturer defined default value is 204
.
This parameter has the configuration ID config_12_2
and is of type INTEGER
.
Sequence On-Off behaviour (timeout)
Behaviour after a rapid sequence of BASIC ON and BASIC OFF commands. The intention is to use a much longer timeout value than the time after a single ON command which should then be followed by a short timeout value.
The behaviour is the same as for parameter 10 (OFF_LOCAL_DISABLE) except: 255 – device ignores ON - OFF sequence and uses OFF behaviour.
Values in the range 0 to 255 may be set.
The manufacturer defined default value is 204
.
This parameter has the configuration ID config_13_2
and is of type INTEGER
.
Sequence Off-On behaviour (timeout)
Behaviour after a rapid sequence of BASIC OFF and BASIC ON commands. The intention is to use a much longer timeout value than the time after a single OFF command which should then be followed by a short timeout value.
The behaviour is the same as for parameter 11 (ON_LOCAL_DISABLE) except: 255 – device ignores OFF - ON sequence and uses ON behaviour.
Values in the range 0 to 255 may be set.
The manufacturer defined default value is 204
.
This parameter has the configuration ID config_14_2
and is of type INTEGER
.
Sequence timing
Time in [100 milliseconds] of maximum delay between BASIC ON and BASIC
OFF (and vice versa) to consider this as a sequence. It is typically 1 second,
but can be exceptionally longer due to retransmissions and overload – in this
case, a longer interval can be allowed (up to 5 seconds).
Values in the range 10 to 50 may be set.
The manufacturer defined default value is 10
.
This parameter has the configuration ID config_15_1
and is of type INTEGER
.
Motion Off behaviour (timeout)
Motion disable timeout after BASIC SET to motion endpoint when the inter-
nal motion sensor is not used for evaluating the behaviour of the lamp (SLAMP)
relay (SPIR) and groups 2 and 3. Events are, however, still transmitted to the
Lifeline, and the device can be controlled via remote motion sensors.
0 = BASIC SET to motion sensor endpoint ignored, BASIC to root is
mapped to relay endpoint, (SPIR) motion sensor still enabled
1 - 209 = Internal motion sensor is disabled for specified timeout after BASIC
SET 0x00 to motion endpoint.
Timeout:
1..100 – 1 second (1) to 100 seconds (100) in 1-second resolution
101..200 – 1 minute (101) to 100 minutes (200) in 1-minute resolution
201..209 – 1 hour (201) to 9 hours (209) in 1-hour resolution
210 - 254 = Reserved
255 = BASIC SET to motion endpoint ignored, motion sensor still disabled. Values in the range 0 to 255 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_16_2
and is of type INTEGER
.
Set the mode for the switch when receiving SWITCH ALL commands.
The following option values may be configured -:
Value | Description |
---|---|
0 | Exclude from All On and All Off groups |
1 | Include in All On group |
2 | Include in All Off group |
255 | Include in All On and All Off groups |
This parameter has the configuration ID switchall_mode
and is of type INTEGER
.
Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.
The IS140-2 supports 5 association groups.
Root
Association group 0 supports 1 node.
The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation. Lifeline
- Device Reset Locally (immediately)
- Notifications:
0x09 (System) – Hardware failure with manufacturer proprietary code (0x03)
0x09 (System) – Software failure with manufacturer proprietary code (0x04)
0x07 (Home security) – Motion Begin event (0x08)
0x07 (Home security) – Motion End event (0x00, 0x08) - Binary Switch Report (SPIR)
- Binary Switch Report (SBIN)
- Multilevel Switch Report (SMUL)
- Multilevel Sensor Report – value of internal ambient light sensor
- Central scene notification (STOGGLE)
Motion Begin and Motion End events are sent along with frames to group 3.
If multichannel association is created the events are sent from motion sensor
endpoint.
Switch Report is sent immediately upon a change of status along with
frames to group 2. If multichannel association is created the events are sent
from lamp/relay endpoint.
Multilevel Sensor Report is sent a maximum of once per 1 minute
(if the value has changed by at least 3%) and a minimum of once per 15 min-
utes (if the value has not changed). If the ambient light value is old (cannot
be measured because of permanent light), the value is not transmitted via
lifeline. Multilevel Sensor Report can also be added to some other events to
send in bulk. If multichannel association is created the events are sent from
light sensor endpoint.
Central scene notification is sent as reaction to user interaction. If multichan-
nel association is created the events are sent from toggle button endpoint.
All notifications to lifeline are sent as sensor states regardless of sensor
settings and states as SLAVE_MODE, LOCAL_DISABLED and MOTION_
ENABLE
Association group 1 supports 1 node.
On/Off control
Group 2 is used for directly controlling Z-Wave devices via BASIC SET com-
mands through the evaluation of movement and light, as with internal use
(so that all of these devices work together). This is intended for use especially
with third-party devices that do not implement reactions for motion events.
BASIC_SET and similar Z-Wave commands are not retransmitted intention-
ally to slaves and must be sent to slave devices via the controlling device
simultaneously. Only for use in master-slave system, multi-device control is
not possible.
Group 2 is evaluated and frames are transmitted there also in SLAVE_
MODE, regardless of LOCAL_DISABLED state and when MOTION_ENABLE
is off (not using internal motion sensor, just reacting to remote motion events
in this case).
If multichannel association is created the events are sent from motion sensor
endpoint.
Association group 2 supports 16 nodes.
Motion Begin/End
Group 3 sends MOTION_BEGIN and MOTION_END frames.
MOTION_BEGIN frame = Notification 0x07 (Home security) –
Motion detection without location (0x08)
MOTION_END frame = Notification 0x07 (Home security) –
Event inactive (0x00, parameter 0x08)
After the first motion detection, MOTION_BEGIN is sent. If continual move-
ment is detected, MOTION_BEGIN is sent every 1 minute repeatedly. When
motion ends, MOTION_END is sent 5 seconds after the last motion detec-
tion.
Notification to group 3 is sent only when NIGHT_MODE = ON and MOTION_
ENABLE = ON, regardless of LOCAL_DISABLE state.
All devices in a group should have the same TIME settings in order that they
switch off at the same time.
If multichannel association is created the events are sent from motion sensor
endpoint.
Association group 3 supports 16 nodes.
Ambient light
Ambient Light via Group 4 is intended to substitute locally measured LUX
values in target devices – so that the network can have one source of ambi-
ent light value. Frames are sent a maximum of once per 2.5 minutes and a
minimum of once per 15 minutes.
When device already uses remote Ambient Light value, then this value is also
retransmitted to group 4.
All devices in such a group should have the same LIGHT (threshold) settings
in order that night mode is detected at the same time.
If multichannel association is created the events are sent from light sensor
endpoint.
Association group 4 supports 15 nodes.
Command Class | Comment |
---|---|
COMMAND_CLASS_NO_OPERATION_V1 | |
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_APPLICATION_STATUS_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_SWITCH_ALL_V1 | |
COMMAND_CLASS_SCENE_ACTIVATION_V1 | |
COMMAND_CLASS_SCENE_ACTUATOR_CONF_V1 | |
COMMAND_CLASS_SENSOR_BINARY_V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL_V4 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_V4 | |
COMMAND_CLASS_CONFIGURATION_V1 | |
COMMAND_CLASS_ALARM_V4 | |
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2 | |
COMMAND_CLASS_POWERLEVEL_V1 | |
COMMAND_CLASS_NODE_NAMING_V1 | |
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V3 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_VERSION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 | |
COMMAND_CLASS_MULTI_CMD_V1 | |
COMMAND_CLASS_MARK_V1 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V2 | |
COMMAND_CLASS_ALARM_V4 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 | |
COMMAND_CLASS_SENSOR_ALARM_V1 |
Command Class | Comment |
---|---|
COMMAND_CLASS_SENSOR_MULTILEVEL_V4 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V2 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_APPLICATION_STATUS_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_SWITCH_ALL_V1 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V2 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.